Original file line number Diff line number Diff line change
Expand Up @@ -111,8 +111,65 @@ For BIM workflows, the validation procedure shall include the following tests:

`[A-Za-z0-9_$]{22} `([IFC base 64](https://standards.buildingsmart.org/IFC/DEV/IFC4_2/FINAL/HTML/schema/ifcutilityresource/lexical/ifcgloballyuniqueid.htm) format)

### Device/Asset type (asset.type)


#### Definition

The device or asset type is a human-generated identifier that is unique for a type of assets to the building. It combines a standard abbreviation for device/asset types and a numerical ID that is unique to each specific device/asset type.

#### Originator

Generated by the BIM operator, design team, project team or facilities team, depending on project stage.

#### Format

```
<X><Z>
```

where:

`X `= <type_abbreviation> (alphabetic characters only, variable length, between 2 and 6 characters)

`Z `= <asset_type_incremental_number> (variable length, unique integer numbers by asset type in each building, non zero padded)

The type abbreviation shall be according to the [Building Device and Asset Abbreviation Registry](https://github.com/theodi/BDNS/blob/master/BDNS_Abbreviations_Register.csv).

The format is composed of a 2 to 6 uppercase alphabetical characters long type abbreviation according to the name abbreviation (`X`) and a variable length character numeric sequence that is unique to the building (`Z`) for each asset type. No leading zeros are allowed in the asset type incremental number to avoid ambiguity.

Only uppercase alphabetic characters and numeric characters are allowed, according to the regular expression below. There is no separator character between the type abbreviation and the incremental number for the `asset.type`.

If there is only one asset type per abbreviation, the asset type incremental number can be omitted.

#### Examples

Asset type example for a lighting fixture asset type: `LT3`

Asset type example for an air handling unit asset type: `AHU10`

Asset type example for a distribution board asset type: `DB7`

Asset type example for a lighting fixture asset type when there is only one type: `LT`

Asset type example for an air handling unit asset type when there is only one type: `AHU`

Asset type example for a distribution board asset type when there is only one type: `DB`


#### Validation tests

The validation procedure shall include the following tests:

1. Regular expression matching to validate the name format.
2. Uniqueness of the name across all asset types in the building.

##### Regular expression matching

```
[A-Z]{2,6}(?:[1-9][0-9]*)?
```

### Device/Asset role name (asset.name)


Expand All @@ -130,12 +187,22 @@ Generated by the BIM operator, design team, project team or facilities team, dep
<X>-<Y>
```

or

```
<XZ>-<Y>
```

where:

`X `= <type_abbreviation> (alphabetic characters only, variable length, between 2 and 6 characters)

`Y `= <building_unique_incremental_number> (variable length, unique integer numbers by building, non zero padded)

`Z `= <asset_type_incremental_number> (variable length, unique integer numbers by asset type in each building, non zero padded)

The use of the `Z` field is optional, only in case there is a need to include `asset.type` definitions.

The type abbreviation shall be according to the [Building Device and Asset Abbreviation Registry](https://github.com/theodi/BDNS/blob/master/BDNS_Abbreviations_Register.csv).

The format is composed of a 2 to 6 uppercase alphabetical characters long type abbreviation according to the name abbreviation (`X`) and a variable length character numeric sequence that is unique to the building (`Y`). No leading zeros are allowed in the building unique incremental number to avoid ambiguity.
Expand All @@ -153,6 +220,11 @@ Name example for an air handling unit: `AHU-3`

Name example for a distribution board: `DB-2`

Name example for a lighting fixture including an asset type: `LT3-375`

Name example for an air handling unit including an asset type: `AHU10-46`

Name example for a distribution board including an asset type: `DB3-21`

#### Validation tests

Expand All @@ -165,10 +237,9 @@ The validation procedure shall include the following tests:


```
[A-Z]{2,6}-[1-9][0-9]*
[A-Z]{2,6}(?:[1-9][0-9]*)?-[1-9][0-9]*
```


## Physical device/asset labels

Physical device/asset labels shall contain the following items:
Expand Down