diff --git a/building_energy_standards_data/database_files/hvac_minimum_requirement_heat_rejection_IECC.json b/building_energy_standards_data/database_files/hvac_minimum_requirement_heat_rejection_IECC.json index 9da4757..d85d129 100644 --- a/building_energy_standards_data/database_files/hvac_minimum_requirement_heat_rejection_IECC.json +++ b/building_energy_standards_data/database_files/hvac_minimum_requirement_heat_rejection_IECC.json @@ -526,533 +526,5 @@ "minimum_performance_gpm_per_hp": 4.5, "minimum_performance_btu_per_hr_per_hp": null, "annotation": "From IECC-2021 TABLE C403.2.3(7)" - }, - { - "template": "IECC-2006", - "equipment_type": "Open Cooling Tower", - "fan_type": "Centrifugal", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 20, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE 503.2.3(11)" - }, - { - "template": "IECC-2006", - "equipment_type": "Open Cooling Tower", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 38.2, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE 503.2.3(11)" - }, - { - "template": "IECC-2006", - "equipment_type": "Closed Cooling Tower", - "fan_type": "Centrifugal", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 20, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE 503.2.3(11)" - }, - { - "template": "IECC-2006", - "equipment_type": "Closed Cooling Tower", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 38.2, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE 503.2.3(11)" - }, - { - "template": "IECC-2006", - "equipment_type": "Air Cooled Condensers", - "fan_type": null, - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 176000, - "annotation": "From TABLE 503.2.3(11)" - }, - { - "template": "IECC-2006", - "equipment_type": "Dry Cooler", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 4, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "Not required by code. Value provided by 90.1 Mechanical Subcommittee" - }, - { - "template": "IECC-2009", - "equipment_type": "Open Cooling Tower", - "fan_type": "Centrifugal", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 20, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE 503.2.3(8)" - }, - { - "template": "IECC-2009", - "equipment_type": "Open Cooling Tower", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 38.2, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE 503.2.3(8)" - }, - { - "template": "IECC-2009", - "equipment_type": "Closed Cooling Tower", - "fan_type": "Centrifugal", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 20, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE 503.2.3(8)" - }, - { - "template": "IECC-2009", - "equipment_type": "Closed Cooling Tower", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 38.2, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE 503.2.3(8)" - }, - { - "template": "IECC-2009", - "equipment_type": "Air Cooled Condensers", - "fan_type": null, - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 176000, - "annotation": "From TABLE 503.2.3(8)" - }, - { - "template": "IECC-2009", - "equipment_type": "Dry Cooler", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 4, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "Not required by code. Value provided by 90.1 Mechanical Subcommittee" - }, - { - "template": "IECC-2012", - "equipment_type": "Open Cooling Tower", - "fan_type": "Centrifugal", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 20, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2012", - "equipment_type": "Open Cooling Tower", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 38.2, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2012", - "equipment_type": "Closed Cooling Tower", - "fan_type": "Centrifugal", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 7, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2012", - "equipment_type": "Closed Cooling Tower", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 14, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2012", - "equipment_type": "Air Cooled Condensers", - "fan_type": null, - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 176000, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2012", - "equipment_type": "Dry Cooler", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 4, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "Not required by code. Value provided by 90.1 Mechanical Subcommittee" - }, - { - "template": "IECC-2015", - "equipment_type": "Open Cooling Tower", - "fan_type": "Centrifugal", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 20, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2015", - "equipment_type": "Open Cooling Tower", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 40.2, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2015", - "equipment_type": "Closed Cooling Tower", - "fan_type": "Centrifugal", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 7, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2015", - "equipment_type": "Closed Cooling Tower", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 14, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2015", - "equipment_type": "Evaporative Condenser", - "fan_type": "Centrifugal", - "test_fluid": "R-507A", - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 135000, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2015", - "equipment_type": "Evaporative Condenser", - "fan_type": "Propeller or Axial", - "test_fluid": "R-507A", - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 157000, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2015", - "equipment_type": "Evaporative Condenser", - "fan_type": "Centrifugal", - "test_fluid": "Ammonia", - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 110000, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2015", - "equipment_type": "Evaporative Condenser", - "fan_type": "Propeller or Axial", - "test_fluid": "Ammonia", - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 134000, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2015", - "equipment_type": "Air Cooled Condensers", - "fan_type": null, - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 176000, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2015", - "equipment_type": "Dry Cooler", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 4, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "NOTE: Not required by code. Value provided by 90.1 Mechanical Subcommittee" - }, - { - "template": "IECC-2018", - "equipment_type": "Open Cooling Tower", - "fan_type": "Centrifugal", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 20, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2018", - "equipment_type": "Open Cooling Tower", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 40.2, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2018", - "equipment_type": "Closed Cooling Tower", - "fan_type": "Centrifugal", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 7, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2018", - "equipment_type": "Closed Cooling Tower", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 16.1, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2018", - "equipment_type": "Evaporative Condenser", - "fan_type": "Centrifugal", - "test_fluid": "R-507A", - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 135000, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2018", - "equipment_type": "Evaporative Condenser", - "fan_type": "Propeller or Axial", - "test_fluid": "R-507A", - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 157000, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2018", - "equipment_type": "Evaporative Condenser", - "fan_type": "Centrifugal", - "test_fluid": "Ammonia", - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 110000, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2018", - "equipment_type": "Evaporative Condenser", - "fan_type": "Propeller or Axial", - "test_fluid": "Ammonia", - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 134000, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2018", - "equipment_type": "Air Cooled Condensers", - "fan_type": null, - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 176000, - "annotation": "From TABLE C403.2.3(8)" - }, - { - "template": "IECC-2018", - "equipment_type": "Dry Cooler", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 4, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "NOTE Not required by code. Value provided by 90.1 Mechanical Subcommittee" - }, - { - "template": "IECC-2021", - "equipment_type": "Open Cooling Tower", - "fan_type": "Centrifugal", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 20, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(7)" - }, - { - "template": "IECC-2021", - "equipment_type": "Open Cooling Tower", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 40.2, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(7)" - }, - { - "template": "IECC-2021", - "equipment_type": "Closed Cooling Tower", - "fan_type": "Centrifugal", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 7, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(7)" - }, - { - "template": "IECC-2021", - "equipment_type": "Closed Cooling Tower", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 16.1, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(7)" - }, - { - "template": "IECC-2021", - "equipment_type": "Evaporative Condenser", - "fan_type": "Centrifugal", - "test_fluid": "R-448A", - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 137000, - "annotation": "From TABLE C403.2.3(7)" - }, - { - "template": "IECC-2021", - "equipment_type": "Evaporative Condenser", - "fan_type": "Propeller or Axial", - "test_fluid": "R-448A", - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 160000, - "annotation": "From TABLE C403.2.3(7)" - }, - { - "template": "IECC-2021", - "equipment_type": "Evaporative Condenser", - "fan_type": "Centrifugal", - "test_fluid": "Ammonia", - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 110000, - "annotation": "From TABLE C403.2.3(7)" - }, - { - "template": "IECC-2021", - "equipment_type": "Evaporative Condenser", - "fan_type": "Propeller or Axial", - "test_fluid": "Ammonia", - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 134000, - "annotation": "From TABLE C403.2.3(7)" - }, - { - "template": "IECC-2021", - "equipment_type": "Air Cooled Condensers", - "fan_type": null, - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": null, - "minimum_performance_btu_per_hr_per_hp": 176000, - "annotation": "From TABLE C403.2.3(7)" - }, - { - "template": "IECC-2021", - "equipment_type": "Dry Cooler", - "fan_type": "Propeller or Axial", - "test_fluid": null, - "start_date": "9/9/1919", - "end_date": "9/9/2999", - "minimum_performance_gpm_per_hp": 4.5, - "minimum_performance_btu_per_hr_per_hp": null, - "annotation": "From TABLE C403.2.3(7)" } ] \ No newline at end of file