In the multizone_office_simple_air test case, a closed damper reports an unusually high airflow. In the provided simulation output, the damper for the Core zone is overridden and set to 0 but the airflow still reports approximately 0.1 m3/s (360 m3/h or 210 CFM).
Typical case/damper leakage is under 10 CFM ( less than 0.005 m3/s) when using the standard1 inWC (250 Pa) of static pressure drop. This would be when tested in accordance to AHRI 880 - 2017 (SI) / AHRI 880 - 2017 (I-P)
My python script to generate the output.csv:
simulator=api("https://api.boptest.net")
test_id=requests.post(
"https://api.boptest.net/testcases/multizone_office_simple_air/select"
).json()["testid"]
print(test_id)
try:
name=requests.get(simulator.name+"/"+test_id).json()["payload"]["name"]
except:
pytest.skip("Unable to confirm the simulator is running.")
raiseifname!="multizone_office_simple_air":
pytest.skip("Incorrect test case is loaded into the simulator.")
print(name)
# Configurationrun_time=60*60*1*1# secondstime_step=60# secondsinputs=dict(
hvac_oveZonActCor_yDam_activate=1,
hvac_oveZonActCor_yDam_u=0,
)
data= {"time_period": "peak_cool_day"}
# Set upmeasurements=dict()
scenario=requests.get(simulator.scenario+"/"+test_id).json()["payload"]
if (
"time_period"notinscenario.keys()
orscenario["time_period"] !=data["time_period"]
):
measurements=requests.put(simulator.scenario+"/"+test_id, data).json()[
"payload"
]
measurements=requests.post(simulator.advance+"/"+test_id, inputs).json()[
"payload"
]
seconds_after_midnight=measurements["time"] %24*60*60ifseconds_after_midnight<8*60*60:
requests.put(
simulator.step+"/"+test_id,
{"step": 8*60*60-seconds_after_midnight},
)
measurements=requests.post(simulator.advance+"/"+test_id, inputs).json()[
"payload"
]
ifrequests.get(simulator.step+"/"+test_id).json()["payload"] !=time_step:
requests.put(simulator.step+"/"+test_id, {"step": time_step})
sim_start_time=measurements["time"]
# Startfor_inrange(0, run_time, time_step):
# Write rule outputs to BOPTEST inputs# Take a step and sleep the remainder of the time stepmeasurements=requests.post(simulator.advance+"/"+test_id, inputs).json()[
"payload"
]
print(measurements)
sim_end_time=measurements["time"]
print("Start times: "+str(sim_start_time))
print("End times: "+str(sim_end_time))
# Get resultsmeasurements_subset= [
"hvac_oveZonActCor_yDam_u",
"hvac_oveZonActEas_yDam_u",
"hvac_oveZonActNor_yDam_u",
"hvac_oveZonActSou_yDam_u",
"hvac_oveZonActWes_yDam_u",
]
measurement_points: dict=requests.get(simulator.measurements+"/"+test_id).json()["payload"]
input_points: dict=requests.get(simulator.inputs+"/"+test_id).json()["payload"]
data= {
#"point_names": [inputs.keys(), measurements_subset],"point_names": [input_points.keys(), measurement_points.keys()],
"start_time": sim_start_time,
"final_time": sim_end_time,
}
output=requests.put(simulator.results+"/"+test_id, data).json()["payload"]
df=pd.DataFrame(output).set_index("time")
df.to_csv("./output.csv")
The text was updated successfully, but these errors were encountered:
As mentioned by @dhblum changing the leakage ratio causes the yearly simulation to increase runtime by 10x, from around 900s to around 9000s, using Dymola2024x. I have not tested with JModelica, but I assume the results will be equivalent or worse (simulation not converging). Furthermore to change the leakage parameter I had to update the Buildings model Buildings.Examples.VAVReheat.BaseClasses.VAVReheatBox, which would require an update to Buildings library . Therefore I think it would be a tricky change to implement until all models are updated to Modelica 4.0 and up to the latest library version, and compiled with different tools.
In the multizone_office_simple_air test case, a closed damper reports an unusually high airflow. In the provided simulation output, the damper for the Core zone is overridden and set to 0 but the airflow still reports approximately 0.1 m3/s (360 m3/h or 210 CFM).
Typical case/damper leakage is under 10 CFM ( less than 0.005 m3/s) when using the standard1 inWC (250 Pa) of static pressure drop. This would be when tested in accordance to AHRI 880 - 2017 (SI) / AHRI 880 - 2017 (I-P)