diff --git a/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml b/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml index 2fb7dbd7c..4d4f96f12 100644 --- a/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/ABSTRACT.yaml @@ -7034,7 +7034,7 @@ CFCM: is_abstract: true uses: - condensing_fan_current_sensor - + CFCM4X: guid: "3b5df213-0616-400f-a025-69e72cda4d7b" description: "Condenser fan current monitoring for 4 fans." @@ -8391,6 +8391,20 @@ WSEBYPVPM: implements: - MONITORING +WSEBYPVM: + guid: "2df125a6-6d00-439d-9aef-4fa3ac6a88c8" + description: "Water side economizer bypass valve monitoring." + is_abstract: true + opt_uses: + - economizer_mode + - sync_economizer_mechanical_cooling_mode + - economizer_bypass_valve_status + - failed_economizer_bypass_valve_alarm + uses: + - economizer_bypass_valve_command + implements: + - MONITORING + MCBYPVPM: guid: "ba06a118-c604-44e8-9ad7-aa5d7cad5e43" description: "Mechanical cooling bypass valve monitoring." @@ -8404,6 +8418,19 @@ MCBYPVPM: implements: - MONITORING +MCBYPVM: + guid: "46a9421b-3902-457f-842c-4849dd45e1dd" + description: "Mechanical cooling bypass valve monitoring." + is_abstract: true + opt_uses: + - economizer_mode + - sync_economizer_mechanical_cooling_mode + - mechanical_cooling_bypass_valve_status + uses: + - mechanical_cooling_bypass_valve_command + implements: + - MONITORING + BYPVFRC: guid: "5c93b3ee-21bb-423c-8c84-9a22ffa1f931" description: "Bypass valve flowrate control." diff --git a/ontology/yaml/resources/HVAC/entity_types/CDWS.yaml b/ontology/yaml/resources/HVAC/entity_types/CDWS.yaml index f4179c87d..a11782e14 100644 --- a/ontology/yaml/resources/HVAC/entity_types/CDWS.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/CDWS.yaml @@ -60,6 +60,15 @@ CDWS_SWTC_BYPVPM: - SWTC - BYPVPM +CDWS_SWTC_WSEBYPVM: + guid: "ba9bfbcf-43b2-42ef-ac60-0fff9a4f4a13" + description: "Condenser water system with supply temperature control and waterside economizing bypass." + is_canonical: true + implements: + - CDWS + - SWTC + - WSEBYPVM + CDWS_SWTC_WDPC_WFRC_HXSWISOVPM: guid: "6f9f09c8-9ccf-4204-a3c8-e24efea95dde" description: "Condenser water system with supply temperature control and isolation valves connected to a heat exchanger." @@ -221,6 +230,18 @@ CDWS_SWTC_WSEBYPVPM: - SWTC - WSEBYPVPM +CDWS_SWTC_WDPC_CLPM_WFRM_MWFRM: + guid: "35a284ef-332d-4e2f-b3f2-4eb94ce3d274" + description: "Chilled water system with supply temperature control, differential pressure control, and thermal load, flowrate and makeup water flowrate monitoring." + is_canonical: true + implements: + - CDWS + - SWTC + - WDPC + - CLPM + - WFRM + - MWFRM + ################################### ### Existing Non-standard Types ### ################################### diff --git a/ontology/yaml/resources/HVAC/entity_types/CH.yaml b/ontology/yaml/resources/HVAC/entity_types/CH.yaml index f9be0c559..35d6f98f6 100644 --- a/ontology/yaml/resources/HVAC/entity_types/CH.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/CH.yaml @@ -106,6 +106,19 @@ CH_SS_SCHWTC_CWDT: - SCHWTC - CWDT +CH_SS_SCHWTC_CHWDPC_CWDT_REFPM_REFSM: + guid: "af499208-82b6-43d3-9f2a-a69facd684c1" + description: "Water-cooled chiller with supply temperature and differential pressure control, condensing water temperature monitoring and refrigerant temperature and pressure monitoring." + is_canonical: true + implements: + - CH + - SS + - SCHWTC + - CHWDPC + - CWDT + - REFPM + - REFSM + CH_SS_RCHWTC_CWDT: guid: "1f0accb9-f2d8-4258-a048-8d3c7a7510d0" description: "Simple water cooled chiller, return water temperature control." @@ -464,6 +477,21 @@ CH_SS_CHWRWISOVPM_SCHWTC_CHWDPM_CDWISOVPM_CWDT_REFPM_REFSM_IGM_CHDXSC: - IGM - CHDXSC +CH_SS_SCHWTC_CHDXSC_CHWDPC_CWDT_REFPM_REFSM_IGM: + guid: "9c8f75a7-8545-46da-91cf-c7da53652f10" + description: "Water-cooled chiller with with supply temperature and differential pressure control, condensing water temperature monitoring, and refrigerant temperature and pressure monitoring." + is_canonical: true + implements: + - CH + - SS + - SCHWTC + - CHDXSC + - CHWDPC + - CWDT + - REFPM + - REFSM + - IGM + CH_SS_SCHWTC_CHWSWISOVM_CHWDPM_CWDT_REFSM_REFPM_IGM_DXSWC: guid: "e3e3ff1b-4d52-4234-aac0-1692fac0ee77" description: "Complex water-cooled chiller." @@ -662,6 +690,25 @@ CH_SS_SCHWTC_CDWFRM_CHWSWISOVM_CWSISOVM_CHWDPM_CHWFRM_CWDT_REFPM_IGM_DXSWC: - IGM - DXSWC + +CH_SS_SCHWTC_CHDXSC_CHWDPM_CHWFRM_CHWRWISOVM_CWDT_CDWFRM_CWRISOVM_REFPM_IGM: + guid: "661834a3-a83f-4f31-94a6-08b0c82992f5" + description: "Complex water-cooled chiller." + is_canonical: true + implements: + - CH + - SS + - SCHWTC + - CHDXSC + - CHWDPM + - CHWFRM + - CHWRWISOVM + - CWDT + - CDWFRM + - CWRISOVM + - REFPM + - IGM + CH_SS_VSC_CHDXSC_SCHWTC_CWSISOVPM_CHWSWISOVM_CHWDPM_CWDT_REFPM_REFSM: guid: "9fd7c871-3378-4a48-898d-3b47fb19d34c" description: "Water cooled chiller with condensing and chilled supply water isolation valves, condensing water temperature differential monitoring, chilled water differential pressure monitoring and single circuit refrigerant pressure and temperature monitoring." @@ -874,6 +921,34 @@ CH_SS_SCHWTC_CHDX2SC_CHWSWISOVM_CDWISOVPM_CWDT: - CDWISOVPM - CWDT +CH_SS_SWTC_DX2SWC_WDPC_RWISOVM_REFSM_REFPM: + guid: "216b01fc-afac-480f-8fc8-130629715587" + description: "Two-stage air-cooled chiller with differential pressure control and refrigerant monitoring." + is_canonical: true + implements: + - CH + - SS + - SWTC + - DX2SWC + - WDPC + - RWISOVM + - REFSM + - REFPM + +CH_SS_SWTC_DX2SWC_WDPM_RWISOVM_REFSM_REFPM: + guid: "6df19046-b117-4523-bd61-518ee6e07e29" + description: "Two-stage air-cooled chiller with differential pressure and refrigerant monitoring." + is_canonical: true + implements: + - CH + - SS + - SWTC + - DX2SWC + - WDPM + - RWISOVM + - REFSM + - REFPM + ################################### ### Existing Non-standard Types ### ################################### diff --git a/ontology/yaml/resources/HVAC/entity_types/CHWS.yaml b/ontology/yaml/resources/HVAC/entity_types/CHWS.yaml index ad70d49d7..3ede4b212 100644 --- a/ontology/yaml/resources/HVAC/entity_types/CHWS.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/CHWS.yaml @@ -525,6 +525,54 @@ CHWS_SS_WDPC_SWISOVPM_BYPVPM_WSEBYPVPM_PWDT_PRSWFRC_SESWTC_SEWFRM_CLPM: - SEWFRM - CLPM +CHWS_PWDT_SESWTC_SEWDPC_SERWFRM_WSEBYPVM: + guid: "2b33f2bf-5b2f-4d73-b8ee-1f35cc08ceb8" + description: "Chilled water system with primary water temperature differential monitoring, secondary supply water temperature and dirrefertial pressure control and water flowrate monitoring, and waterside economizer bypass valve." + is_canonical: true + implements: + - CHWS + - PWDT + - SESWTC + - SEWDPC + - SERWFRM + - WSEBYPVM + +CHWS_SWTC_WDPC_BYPVFRC_WSEBYPVM_MCBYPVM_CLPM: + guid: "dc89a367-2774-4564-864f-c66da0ab8a86" + description: "Chilled water system with differential pressure control, mechanical cooling bypass, waterside economizer bypass and cooling thermal power monitoring." + is_canonical: true + implements: + - CHWS + - SWTC + - WDPC + - BYPVFRC + - WSEBYPVM + - MCBYPVM + - CLPM + +CHWS_SWTC_WDPC_BYPVFRC_WSEBYPVM_MCBYPVM: + guid: "36602528-dfbb-4922-aeae-ba756be83d55" + description: "Chilled water system with differential pressure control, mechanical cooling bypass and waterside economizer bypass." + is_canonical: true + implements: + - CHWS + - SWTC + - WDPC + - BYPVFRC + - WSEBYPVM + - MCBYPVM + +CHWS_SESWTC_SEWDPC_SEWFRM_WSEBYPVM: + guid: "503d5173-65a9-422a-9788-c7c00f2196a2" + description: "Chilled water system with secondary supply water temperature and differential pressure control and waterside economizer bypass." + is_canonical: true + implements: + - CHWS + - SESWTC + - SEWDPC + - SEWFRM + - WSEBYPVM + ################################### ### Existing Non-standard Types ### ################################### diff --git a/ontology/yaml/resources/HVAC/entity_types/CT.yaml b/ontology/yaml/resources/HVAC/entity_types/CT.yaml index 2ed4999d1..da3126851 100644 --- a/ontology/yaml/resources/HVAC/entity_types/CT.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/CT.yaml @@ -43,6 +43,16 @@ CT_SS_VSC_SWTC: - VSC - SWTC +CT_SS_VSC_SPSS: + guid: "ca45be7c-2ac7-45b1-804a-d7160bd5a0e2" + description: "Variable speed cooling tower with onboard spray pump." + is_canonical: true + implements: + - CT + - SS + - VSC + - SPSS + CT_SS_SPSS_SWTC_RWISOVM: guid: "2fc17f81-1b4f-43ed-a5ac-b728527dd2b0" description: "Evaporative cooler with onboard spray pump." @@ -176,6 +186,17 @@ CT_SS_RWISOVM_SWISOVM_SWTM: opt_uses: - low_level_status +CT_SS_VSC_SWTC_SPSS: + guid: "ad3c6e1b-1a16-4564-a8b6-a56168daceaa" + description: "Cooling tower with onboard spray pump and variable speed control." + is_canonical: true + implements: + - CT + - SS + - VSC + - SWTC + - SPSS + CT_SS_VSC_SPSS_SWTC_RWISOVM: guid: "226b9d4e-cdf7-4106-bfd4-4b8a5e5a55c4" description: "Cooling tower with onboard spray pump and variable speed control." @@ -188,6 +209,19 @@ CT_SS_VSC_SPSS_SWTC_RWISOVM: - SWTC - RWISOVM +CT_SS_VSC_SPSS_SWTC_SWISOVM_BWFRM: + guid: "368e7cef-75e2-407c-ac2b-3904a357b825" + description: "Cooling tower with onboard spray pump, variable speed control, isolation on supply side and blowdown water flow monitoring." + is_canonical: true + implements: + - CT + - SS + - VSC + - SPSS + - SWTC + - SWISOVM + - BWFRM + CT_SS_VSC_SWTM_RWISOVM_SWISOVM_FSWISOVM_FRWISOVM: guid: "9ca0256a-9d7f-4b4d-8289-e321e487a2a1" description: "Cooling tower with variable speed control, supply and return isolation valves and supply temp monitoring, supply and return filter isolation valves and supply water temperature monitoring." diff --git a/ontology/yaml/resources/HVAC/entity_types/DC.yaml b/ontology/yaml/resources/HVAC/entity_types/DC.yaml index 9662d7449..50e752dbc 100644 --- a/ontology/yaml/resources/HVAC/entity_types/DC.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/DC.yaml @@ -25,6 +25,17 @@ DC_SS_SWTC: - SS - SWTC +DC_SS_VSC_SWTC_RWISOVM: + guid: "49987aa9-de99-4ff2-94a8-eca95b39ea3b" + description: "Typical dry-cooler (closed loop sensible cooler) with isolation on return side." + is_canonical: true + implements: + - DC + - SS + - VSC + - SWTC + - RWISOVM + DC_SS_FSS4X_FVSC4X_SWTC_WDPM: guid: "1e1ddaf9-d9e7-46c2-8026-964c183a22c4" description: "Closed loop sensible cooler with four fans and differential pressure monitoring." diff --git a/ontology/yaml/resources/HVAC/entity_types/HX.yaml b/ontology/yaml/resources/HVAC/entity_types/HX.yaml index e32648933..50c95b56d 100644 --- a/ontology/yaml/resources/HVAC/entity_types/HX.yaml +++ b/ontology/yaml/resources/HVAC/entity_types/HX.yaml @@ -58,6 +58,28 @@ HX_CHWDT_CHWRWISOVM: - CHWDT - CHWRWISOVM +HX_CHWDT_CWRISOVM_CHWRWISOVM_CLPM: + guid: "c1035031-6ab6-4501-b600-bd89deafd83b" + description: 'Chilled water heat exchanger with isolation on condensing and chilled return side, and cooling thermal power monitoring.' + is_canonical: true + implements: + - HX + - CHWDT + - CWRISOVM + - CHWRWISOVM + - CLPM + +HX_CHWDT_CWDT_CHWRWISOVM_CLPM: + guid: "1f7f5457-22a3-4889-9101-1b82fdf44edf" + description: 'Chilled water heat exchanger with chilled and condensing water temperature differential monitoring, isolation on chilled return side, and cooling thermal power monitoring.' + is_canonical: true + implements: + - HX + - CHWDT + - CWDT + - CHWRWISOVM + - CLPM + HX_CHWDT_CHWRWISOVPM: guid: "29bca835-c90f-4d75-bc1c-e3c6c449f476" description: "Chilled water heat exchanger." @@ -263,6 +285,16 @@ HX_PSWTC_CHWDT_CHWRWISOVPM: guid: "aee0a0be-f0fe-458a-9d70-d37eba78e401" description: "Chilled/process water heat exchanger with isolation valve on chilled return water side." is_canonical: true + implements: + - HX + - PSWTC + - CHWDT + - CHWRWISOVPM + +HX_PSWTC_CHWDT_CHWRWISOVM: + guid: "aacf282a-0d24-4c00-9ad9-91988d0b80a3" + description: "Chilled/process water heat exchanger with isolation valve on chilled return water side." + is_canonical: true implements: - HX - PSWTC diff --git a/ontology/yaml/resources/fields/telemetry_fields.yaml b/ontology/yaml/resources/fields/telemetry_fields.yaml index 001eaeb61..37d3ebe6b 100644 --- a/ontology/yaml/resources/fields/telemetry_fields.yaml +++ b/ontology/yaml/resources/fields/telemetry_fields.yaml @@ -625,6 +625,18 @@ literals: - economizer_bypass_valve_percentage_sensor: fixed_min: 0 fixed_max: 100 +- economizer_bypass_valve_command: + - OPEN + - CLOSED +- economizer_bypass_valve_status: + - OPEN + - CLOSED +- mechanical_cooling_bypass_valve_command: + - OPEN + - CLOSED +- mechanical_cooling_bypass_valve_status: + - OPEN + - CLOSED - mechanical_cooling_bypass_valve_percentage_command: fixed_min: 0 fixed_max: 100