#!/usr/bin/python3
# Author: Danny De Gaspari
import lib_hvac
AC_Fan = ['auto', 'off', 'low', '', 'med', 'high']
AC_Mode = ['auto', 'cool', 'dry', 'fan', 'heat']
class AC_Unit():
address = 0
on_off = 0
settemp = 0
usedtemp = 0
roomtemp = 0
roomtempacc = 0
fan = 0
swing = 0
mode = 0
def __init__(self, address):
self.address = address
def get_status(units):
ser = lib_hvac.ser_open()
if ser == -1:
return -1
for unit in units:
cmd_52 = False
cmd_53 = False
cmd_64 = False
collect_info = True
while collect_info:
serline = lib_hvac.ser_capture_hvac_msg(ser)
if (serline[lib_hvac.PROTOCOL_SOURCE_POS] == unit.address):
if (serline[lib_hvac.PROTOCOL_COMMAND_POS] == 0x52):
cmd_52 = True
unit.settemp = (serline[lib_hvac.PROTOCOL_DATA1_POS] & 0x3f) + 9
unit.roomtemp = (serline[lib_hvac.PROTOCOL_DATA2_POS] & 0x3f) + 9
unit.fan = (serline[lib_hvac.PROTOCOL_DATA4_POS] & 0x07)
unit.swing = (serline[lib_hvac.PROTOCOL_DATA4_POS] & 0xf8) != 0xF8
unit.on_off = (serline[lib_hvac.PROTOCOL_DATA5_POS] & 0x80) == 0x80
if (serline[lib_hvac.PROTOCOL_COMMAND_POS] == 0x53):
cmd_53 = True
unit.mode = (serline[lib_hvac.PROTOCOL_DATA8_POS] & 0x07)
if (serline[lib_hvac.PROTOCOL_COMMAND_POS] == 0x64):
cmd_64 = True
unit.usedtemp = (serline[lib_hvac.PROTOCOL_DATA3_POS] * 256 + serline[lib_hvac.PROTOCOL_DATA4_POS] - 553) / 10.0
unit.roomtempacc = (serline[lib_hvac.PROTOCOL_DATA5_POS] * 256 + serline[lib_hvac.PROTOCOL_DATA6_POS] - 553) / 10.0
collect_info = not(cmd_52 and cmd_53 and cmd_64)
lib_hvac.ser_close(ser)
return 0
if __name__== "__main__":
units = [AC_Unit(0x20), AC_Unit(0x21)]
print ('Reading status...')
if get_status(units) != -1:
for unit in units:
print ('\nUnit: 0x%x' % unit.address)
print ('Power :', unit.on_off)
print ('Set temp :', unit.settemp)
print ('Room temp :', unit.roomtemp)
print ('Used temp :', unit.usedtemp)
print ('Acc Room temp :', unit.roomtempacc)
if unit.on_off:
print ('Fan :', AC_Fan[unit.fan])
print ('Swing :', unit.swing)
print ('Mode :', AC_Mode[unit.mode])
else:
print ('Status get failed')